Works Series Commercial & Industrial Energy Systems
The CIES-6030 is a high-efficiency energy storage solution with a 61.44 kWh capacity, engineered for commercial and industrial applications. It integrates a hybrid inverter, advanced battery management system (BMS), and energy management system (EMS), ensuring peak power regulation, emergency backup, and cost-efficient energy storage. Designed for outdoor installations, it offers strong environmental adaptability with flexible installation options.
Product Model: CIES-6030 | Check full specifications on datasheet
Available to registered users after login/registration is enabled.
| Property | Value | Unit |
|---|---|---|
| Rated Voltage | 307.2 | V |
| Rated Energy | 61440 | Wh |
| Battery System | ||
| System Model | CIES 6030 | - |
| Application | Backup Power | - |
| Configuration | 96S1P | - |
| Cooling Method | Air Cooling | - |
| Rated Capacity | 200 | Ah |
| Charge/Discharge Port | Same Port | - |
| Communication Port | CAN / RS485 | - |
| Max Series Connection | 6 | - |
| Overcharge Protection Voltage | 336 | V |
| Discharge Protection Voltage | 268.8 | V |
| Cell Charge Protection Voltage | 3.5 | V |
| Cell Discharge Protection Voltage | 2.8 | V |
| Charge Temperature Range | 0 ~ 60 | °C |
| Discharge Temperature Range | -20 ~ 65 | °C |
| Max Continuous Charge Current | 100 | A |
| Max Continuous Discharge Current | 200 | A |
| Discharge Overcurrent Protection | 225 | A |
| Cycle Life | ≥4000 cycles (80% DOD, 0.2C @ 25°C) | - |
| Battery Box Dimensions | 442 x 660 x 230 | MM |
| Battery Box Weight | 90 (±5) | Kg |
| ESS System - PV Parameters | ||
| PV Max Power | 19.2 + 19.2 | kW |
| PV Max Voltage | 850 | V |
| PV Start Voltage | 250 | V |
| MPPT Voltage Range | 200 ~ 830 | V |
| PV Max Current | 32 + 32 | A |
| ESS System - AC Grid Parameters | ||
| Rated Power | 30 | KVA |
| Rated Current | 33.5 | A |
| Rated Grid Voltage | 400 / 230 | V |
| Grid Voltage Range | -20% ~ +15% | - |
| Grid Frequency Range | 50Hz (47~52Hz) / 60Hz (57~62Hz) | - |
| Current Harmonics | <5% (Over 30% Load) | - |
| Power Factor | -0.8 ~ +0.8 | - |
| ESS System - AC Off-Grid Parameters | ||
| Rated Output Power | 30 | KVA |
| Max Output Power | 33 | KVA |
| Rated Output Current | 43.5 | A |
| Max Output Current | 48 | A |
| Rated Output Voltage | 400 / 230 | V |
| Output Voltage Harmonics | <3% (Resistive Load) | - |
| Unbalance Capability | 100% | - |
| Frequency Range | 50 / 60 | Hz |
| Output Overload Capacity | 48A < I ≤ 54A / 100s, 54A < I ≤ 65A / 100ms | - |
| ESS System - General | ||
| Maximum Efficiency | 97.8 | % |
| Standby Power | <10 | W |
| No-Load Power | <100 | W |
| Ingress Protection | IP54 | - |
| Altitude | 2000m (3000m/4000m derate 90%/80%) | - |
| Communication Protocol | CAN or RS485 | - |
| Environmental Characteristics | ||
| Operating Temperature | 0 ~ 50 | °C |
| Operating Temperature | -20 ~ 55 | °C |
| Recommended Operating Temperature | 23 ± 2 | °C |
| Storage Temperature | -10 ~ 45 | °C |
| Storage Temperature | 0 ~ 35 | °C |
| Storage Temperature | 10 ~ 25 | °C |
| Relative Humidity | 65 ± 20% RH | - |